Warehouse-FBL-100

ICG FBL-200 is a water-based, thin-film, intumescent coating that is a combination of the latest technologies creating the world’s leading Fire Barrier Latex.  FBL-200 is UL/ULC tested and certified UL263. it is a unique intumescent fire protection that provides an attractive decorative finish. Applies easily in a wide range of environments. Zero VOC. Crack, delamination and discoloration free. FBL-200 can be applied on Aluminum, Dimensional lumber, Manufactured wood products, Trusses, Drywall, Spray polyurethane, HDPE wall panels, Concrete and Structural Steel. It has been specifically designed for structural steel with a slow carbon char expansion allowing for a 2 hour ratings.

Product Category: Fire Protection Category

Product Chemistry: ACRYLIC COPOLYMER LATEX

Volume Solids: 71.44 %

Specific Gravity: 1.37

VOC: 3 g/L

Density: 1442 g/L

Average Coating Pull-Off Strength: 400 psi

D2240-05(10) Hardness test: 77

ASTM D2486 and D3450 Scrub Resistance: 172 Cycles

Percent Water Content: 28.46%

UL 263: Design Number Y641

Please click the link to download a PDF version of FBL-200 Product Data Sheet

Please click the link to download a PDF version of FBL-200 Safety Data Sheet

Please click the link to download a PDF version of FBL-200 Application Guide

Please click the link to download a PDF version of FBL-200 VOC, Density, Weight Solids and Percent Water Test Results

Please click the link to download a PDF version of FBL-200 Scrub Resistance Test Results

Design No. Y641
BXUV.Y641

Fire-resistance Ratings – ANSI/UL 263

BXUV – Fire Resistance Ratings – ANSI/UL 263
BXUV7 – Fire Resistance Ratings – CAN/ULC-S101 Certified for Canada
See General Information for Fire-resistance Ratings – ANSI/UL 263

See General Information for Fire Resistance Ratings – CAN/ULC-S101 Certified for Canada

Design No. Y641
April 28, 2017

Ratings — 1, 1-1/2, and 2 Hr. (See Item 3)
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

1. Steel Column — Min. W8x48 wide flange steel column. Columns shall be free of dirt, loose scale and oil.

2. Primer Coating — Approx. dry film thickness of 3 mil thickness of Sherwin Williams type Kem Bond HS primer.

3. Mastic and Intumescent Coatings* — One component spray material applied in one or more coats as described in the application instructions to the thicknesses shown below. Thicknesses below include the 3 mil of primer.

Steel Size W/D HP/A Min. Thickness Rating, Hour
inch mm
W8x48 1.00 0.29 0.072 1.83 1
W8x48 1.00 0.29 0.147 3.73 1-1/2
W8x48 1.00 0.29 0.222 5.64 2

INTERNATIONAL COATINGS GROUP INC — Type FBL-200. Investigated for Conditioned Interior Space Purpose and Interior General Purpose Use.

4. Topcoat — (Not Shown) — Sherwin Williams type DTM acrylic top coat applied at a minimum thickness of 6 mil over the intumescent material.

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.